一、产品说明
Installed in the main distribution boards of buildings or power inlet where lightning current may enter.
It is mainly used to withstand lightning current surges.
Nominal waveform: 10/350 μs.
Suitable for sites with external lightning protection system and risk of direct lightning current intrusion.
Monoblock Multi-Pole SPD — Class I·Class II · Type 1·Type 2 模块式多极电涌保护器 — I类+II类 · 1型+2型
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Location of Use |
使用位置 |
Main Distribution Boards 主配电盘 |
|
Network Systems |
适用电网系统 |
TT, TN-S |
|
Mode of Protection |
保护模式 |
L-N / L-PE, N-PE |
|
Surge Ratings |
电涌防护等级 |
Iimp = 25 kA / 100 kA (10/350μs); In = 25 kA / 100 kA (8/20μs) |
|
IEC/EN Category |
IEC/EN 分类 |
Class I+II / Type 1+2 |
|
Protective Elements |
保护元件 |
High Energy MOV and GDT 高能压敏电阻+气体放电管 |
|
Housing |
外壳结构 |
Monoblock Design 整体式设计 |
|
Compliance |
合规标准 |
IEC 61643-11:2025; EN 61643-11:2025 |
二、Technical Data — IEC Electrical | 技术参数 — IEC 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Nominal AC Voltage (50/60Hz) (L-N) |
额定交流电压(L-N) |
120V / 230V / 385V |
|
Max. Continuous Operating Voltage (L-N) Uc |
最大持续运行电压(L-N) |
150V / 275V / 385V |
|
Max. Continuous Operating Voltage (N-PE) Uc |
最大持续运行电压(N-PE) |
255V |
|
Nominal Discharge Current (L-N)/(N-PE) In |
标称放电电流(L-N/N-PE) |
25 kA / 100 kA |
|
Max. Discharge Current (L-N)/(N-PE) Imax |
最大放电电流(L-N/N-PE) |
100 kA |
|
Impulse Discharge Current (L-N)/(N-PE) Iimp |
冲击放电电流(L-N/N-PE) |
25 kA / 100 kA |
|
Total Discharge Current Itotal |
总放电电流 |
100 kA |
|
Specific Energy (L-N)/(N-PE) W/R |
比能量 |
156 kJ/Ω / 2.5 MJ/Ω |
|
Charge (L-N)/(N-PE) Q |
电荷量 |
12.5 As / 50 As |
|
Voltage Protection Level (L-N)/(N-PE) Up |
电压保护水平 |
1000/1500V; 1500/1500V; 1600/1500V; 1800/1500V |
|
Follow Current Interrupting Rating Ifi |
后续电流开断能力 |
100 Arms |
|
Response Time (L-N)/(N-PE) tA |
响应时间 |
< 25 ns / < 100 ns |
|
Back-Up Fuse (max) |
后备保护熔断器(最大) |
315 A gL/gG |
|
Short-Circuit Current Rating (L-N) IsccR |
短路电流耐受能力(L-N) |
50 kA |
|
TOV Withstand 5s (L-N) UT |
暂时过电压耐受5秒(L-N) |
180V / 335V / 335V |
|
TOV Withstand 120min (L-N) UT |
暂时过电压耐受120分钟(L-N) |
230V / 440V / 440V |
|
TOV Withstand 200ms (N-PE) UT |
暂时过电压耐受200ms(N-PE) |
1200V |
三、内部配置
四、尺寸与包装
五、连接图
六、安装说明 Installation Instruction
安装位置:建筑物总配电柜、电源进线主配电盘,雷电流可能直接进入的电源入口处。
Installation Location: Building main distribution cabinet, main power incoming distribution board, power inlet where lightning current may intrude directly.
接线方式:3+NPE 接线,3 根相线 + N 线 + PE 保护地线,保护模式 L-N、L-PE、N-PE。
Wiring Method: 3+NPE wiring, 3 phase lines + N line + PE protective earth wire, protection mode L-N, L-PE, N-PE.
配套要求:前端需配置后备保护熔断器(最大 315A gL/gG);按配电系统短路参数选型。 Matching requirement: Back-up protection fuse shall be equipped at front end (max.315A gL/gG); select according to short-circuit parameters of power distribution system.
接地要求:PE 线可靠连接至建筑物总等电位接地端子,接地线尽量短直,降低引线电感。
Earthing Requirement: PE wire shall be reliably connected to building main equipotential bonding terminal. Earthing conductor shall be as short and straight as possible to reduce lead inductance.
安装环境:室内配电柜内安装,避开潮湿、腐蚀、高温强振动环境。
Installation Environment: Install inside indoor distribution cabinet, keep away from humid, corrosive, high temperature and strong vibration environment.
七、应用场景 Application Scenarios
适用于带有外部防雷装置(避雷针 / 避雷带)的建筑物,存在直接雷电流引入风险的电源进线系统。 Suitable for buildings equipped with external lightning protection system (lightning rod/lightning belt), power incoming system with risk of direct lightning current intrusion.
建筑物总配电房、大楼电源总进线柜,作为一级电源防雷保护。
Building main power distribution room, main incoming cabinet of building power supply, for primary power lightning protection.
通信机房、数据中心、工厂厂区、医院、学校等重要建筑总电源入口防雷。
Lightning protection for main power inlet of communication room, data center, factory area, hospital, school and other important buildings.
新能源、光伏、风电等配套总配电系统,直击雷防护。
Main power distribution system of new energy, photovoltaic, wind power and other supporting projects for direct lightning protection.