GH-2型11米单管钢管避雷塔技术文档
产品简介: Technical Documentation for GH-2 Type 11-Meter Single-Pipe Steel Lightning Rod Tower

GH-2型11米单管钢管避雷塔技术文档

Technical Documentation for GH-2 Type 11-Meter Single-Pipe Steel Lightning Rod Tower

一、产品概述

1. Product Overview

10

GH-2型避雷塔是依据国标图集 15D501(及早期99D501-1) 制造的标准 11米 自立式单管钢管避雷塔,属于GH系列中 适配0.4 kN/m²常规风压的基础轻载型号。塔体为单根锥形钢管,无拉索,塔体本身兼作引下线,外形简洁,底部占地面积远小于同高度桁架塔。

公开规格表显示,GH-2与GH-1在11米高度下共享同一组核心参数:底盘直径 362mm,塔体参考重量 305kg(5mm壁厚)。这一配置适用于0.4 kN/m²常规风压工况;若项目处于0.7 kN/m²高风压区,建议选用同系列6mm壁厚规格(364kg级)并对杆体及基础进行复核。底部基础采用 JD-1 独立基础,预埋螺栓 M24×8,土建开挖量极小。塔顶可配套主动预放电接闪装置及机械式雷电计数器。本型号适用于 楼顶、小型库房、泵房、通信基站及场地受限的常规防雷场景。

The GH-2 lightning protection tower is a standard 11-meter self-supporting single-pipe steel lightning tower manufactured in accordance with national standard atlas 15D501 (and earlier 99D501-1). It is the basic light-duty model in the GH series for a conventional wind pressure of 0.4 kN/m². The tower body is a single tapered steel pipe without guy wires, and the tower body itself serves as the down conductor. The appearance is clean, and the base footprint is much smaller than truss towers of the same height.

Public specification tables show that GH-2 and GH-1 share the same core parameters at 11 meters: base plate diameter 362 mm and reference tower weight 305 kg (5 mm wall thickness) . This configuration is suitable for 0.4 kN/m² conventional wind pressure. For projects in 0.7 kN/m² high-wind-pressure areas, the 6 mm wall thickness specification (364 kg class) in the same series is recommended, with verification of the pole body and foundation. The foundation is JD-1 independent footing with M24×8 anchor bolts, requiring minimal civil excavation. The tower top can accommodate Jielitong active pre-discharge air terminals and mechanical lightning counters. This model is suitable for rooftops, small warehouses, pump rooms, communication base stations, and space-constrained conventional lightning protection scenarios.

二、执行规范标准

  1. Applicable Codes and Standards

GB 50057-2010《建筑物防雷设计规范》
GB 50057-2010 Code for Design Protection of Structures Against Lightning

GB 50135-2019《高耸结构设计标准》
GB 50135-2019 Standard for Design of High-Rising Structures

GB 50009-2012《建筑结构荷载规范》
GB 50009-2012 Load Code for the Design of Building Structures

GB 50011-2010(2016版)《建筑抗震设计规范》
GB 50011-2010 (2016 Edition) Code for Seismic Design of Buildings

GB/T 13912-2002《金属覆盖层 钢铁制件热浸镀锌层技术要求及试验方法》
GB/T 13912-2002 Metallic Coatings—Hot Dip Galvanized Coatings on Fabricated Iron and Steel Articles—Specifications and Test Methods

CECS 80:2006《塔桅钢结构工程施工质量验收规程》 (垂直度验收依据,第9.6.2条单管塔专项条款)
CECS 80:2006 Specification for Construction Quality Acceptance of Tower and Mast Steel Structures (Basis for verticality acceptance, Article 9.6.2 for single-pipe towers)

15D501《建筑物防雷设施安装》国家建筑标准设计图集
15D501 Installation of Lightning Protection Facilities for Buildings, National Building Standard Design Atlas

IEC 62305《雷电防护》国际标准
IEC 62305 Protection against Lightning - International Standard

三、塔体核心技术参数(多源交叉验证)

  1. Core Technical Parameters of Tower Body (Multi-source Cross-verified)

塔型:GH单管锥形钢管避雷塔(塔体兼作引下线),总高度 11m。
Tower type: GH single-pipe tapered steel tube lightning tower (tower body serves as down conductor), total height 11m.

主材材质:Q235B碳素结构钢;锥形钢管整体热浸镀锌,锌层厚度 ≥85μm(符合GB/T 13912),满足户外长期防腐需求。
Main material: Q235B carbon structural steel; tapered steel pipe integrally hot-dip galvanized, zinc coating thickness ≥85μm (per GB/T 13912), meeting long-term outdoor anti-corrosion requirements.

截面与壁厚:锥形截面,上口直径 190mm,底盘直径 362mm。标准配置壁厚 5mm(对应305kg级);0.7 kN/m²高风压场景建议选用 6mm 壁厚(364kg级)。
Section and wall thickness: tapered section, top diameter 190mm, base plate diameter 362mm. Standard wall thickness 5mm (305kg class); for 0.7 kN/m² high wind pressure, 6mm wall thickness (364kg class) is recommended.

重量:305kg(5mm壁厚标准配置,塔体参考重量,不含基础及附件)。同系列6mm壁厚规格参考重量为 364kg。
Weight: 305kg (5mm wall standard configuration, reference tower weight excluding foundation and accessories). The 6mm wall specification in the same series has a reference weight of 364kg.

设计基本风压:0.4 kN/m²(标准配置适配工况)。0.7 kN/m²工况下建议选用6mm壁厚规格并复核杆体与基础。
Basic design wind pressure: 0.4 kN/m² (standard configuration adaptation). For 0.7 kN/m², the 6mm wall specification is recommended with pole and foundation verification.

地基承载特征值:≥100 kN/m²(JD-1基础按100 kN/m²档位配置;150 kN/m²档位亦在适用范围内,可根据地勘优化基础配筋)。
Characteristic value of foundation bearing capacity: ≥100 kN/m² (JD-1 foundation configured for the 100 kN/m² tier; the 150 kN/m² tier is also applicable, allowing foundation reinforcement optimization based on geotechnical survey).

配套基础:JD-1 现浇混凝土独立基础。基础尺寸 a=650mm,b=800mm,埋深 2.0m,基础体积 0.845m³。预埋螺栓 M24×8。基础顶面荷载标准值:Mk=12.106 kN·m,Nk=4.939 kN,Qk=2.611 kN。混凝土强度等级建议不低于 C25,垫层C15。
Supporting foundation: JD-1 cast-in-place concrete isolated foundation. Dimensions a=650mm, b=800mm, embedment depth 2.0m, volume 0.845m³. Anchor bolts M24×8. Foundation top load standard values: Mk=12.106 kN·m, Nk=4.939 kN, Qk=2.611 kN. Concrete grade not lower than C25, with C15 blinding.

防腐方式:整体热浸镀锌,锌层厚度 ≥85μm。在标准工业大气及一般户外环境中,满足25年以上防腐需求。
Anti-corrosion method: integrally hot-dip galvanized, zinc coating thickness ≥85μm. In standard industrial atmospheres and general outdoor environments, it meets anti-corrosion requirements of more than 25 years.

垂直度控制:安装完成后单管塔整体垂直度偏差 ≤H/1500(即≤7.3mm) ,依据 CECS 80:2006第9.6.2条(单管塔专项条款)。该条款原文为“单管塔的整体垂直度偏差不应大于H/1500”,与塔架通用的第9.5.5条并列,单管塔以第9.6.2条为准。部分厂家资料标注的“≤1/1000”与CECS 80规范条文不一致,本文件采用规范值作为验收口径。
Verticality control: after installation, the overall verticality deviation of the single-pipe tower shall be ≤H/1500 (i.e., ≤7.3mm), per Article 9.6.2 of CECS 80:2006 (single-pipe tower clause). The original text states “the overall verticality deviation of a single-pipe tower shall not exceed H/1500,” parallel to Article 9.5.5 for general tower frames; for single-pipe towers, Article 9.6.2 governs. Some manufacturer data indicate “≤1/1000,” which is inconsistent with the CECS 80 code provision; this document adopts the code value as the acceptance criterion.

使用寿命:正常户外环境(热镀锌层完好、无强腐蚀介质)设计使用年限 ≥25年。
Service life: design service life ≥25 years under normal outdoor environment (intact galvanized coating, no highly corrosive media).

四、全套防雷配套产品清单(含精准数量)

4. Jielitong Complete Lightning Protection Accessory Product List (with Precise Quantities)

说明:以下数量为基于常规土壤(土壤电阻率≤300Ω·m)的标准配置参考。实际工程中应根据现场实测土壤电阻率及地勘报告,由技术团队出具定制化接地配置方案。
Note: The following quantities are a reference standard configuration based on conventional soil (soil resistivity ≤ 300Ω·m). In actual projects, Jielitong's technical team should issue a customized grounding configuration scheme based on the measured on-site soil resistivity and geotechnical report.

(一)接闪与引下部分

(1) Air Termination and Down-Conductor Part

主动预放电避雷针(ESE) :1套。安装于塔顶。其保护半径的提升源于提前上行先导特性,按NF C 17-102标准计算;该性能描述不作为GB 50057滚球法设计的强制依据,但能为楼顶、小型库房等有限空间提供更大的防雷安全裕度。
Active pre-discharge air terminal (ESE): 1 set. Installed at the tower top. The protection radius enhancement originates from the early upward leader characteristic, calculated per NF C 17-102; this performance description is not a mandatory basis for rolling-sphere design under GB 50057 but provides a larger lightning protection safety margin for rooftops and small warehouses with limited space.

利用塔体本体作为引下线:GH-2的钢管塔体本身即为引下通路,无需额外敷设专用引下线。法兰连接处须保证可靠电气连通(跨接或法兰面直接接触电阻≤0.03Ω)。
Tower body as down conductor: The steel pipe body of GH-2 serves as the down-conductor path; no separate dedicated down conductor is required. Flange connections must ensure reliable electrical continuity (bonding or direct flange contact resistance ≤0.03Ω).

断接卡(测试点) :1套。安装于距地面1.5m~1.8m处,便于防雷年检时断开测量接地电阻。
Disconnect clamp (test point): 1 set. Installed at 1.5m~1.8m above ground for convenient disconnection and grounding resistance measurement during annual lightning protection inspections.

(二)智能监测部分(可选配)

(2) Intelligent Monitoring Part (Optional)

机械式雷电计数器:1台。安装于断接卡上方直线段,感应并记录雷击次数,无需外部供电。
Mechanical lightning counter: 1 unit. Installed on the straight section above the disconnect clamp to sense and record lightning strikes without external power supply.

(三)特种接地系统部分(防雷验收的核心)

(3) Special Grounding System Part (Core of Lightning Protection Acceptance)

水平接地干线:25m。采用 -40×4热镀锌扁钢,围绕JD-1基础外围敷设,形成环形地网。
Horizontal grounding main: 25m. Made of -40×4 hot-dip galvanized flat steel, laid around the periphery of the JD-1 foundation to form a ring grounding grid.

空腹式离子接地极:2根。每根长3m,在基础两侧对称布置,垂直打入地下。
Jielitong hollow ion grounding electrodes: 2 rods. Each is 3m long, symmetrically arranged on both sides of the foundation and driven vertically into the ground.

零欧复合接地体:2套。配合离子接地极使用,增大散流面积。
Zero-ohm composite grounding bodies: 2 sets. Used together with ion grounding electrodes to increase current-dissipation area.

高纯物理降阻剂:100kg。回填接地沟槽,确保系统达标。
High-purity physical resistance-reducing agent: 100kg. Used for backfilling grounding trenches to ensure compliance.

等电位连接排:1块。镀锡铜排,安装于塔脚或设备机架,用于设备接地汇集。
Equipotential bonding bar: 1 piece. Tin-plated copper bar, installed at the tower foot or equipment rack for equipment grounding convergence.

接地电阻目标:依据GB 50057-2010第4.2.1条第8款,独立接闪杆每一引下线的 冲击接地电阻不宜大于10Ω。实际工频电阻需按GB 50057-2010附录C换算后判定。配置方案以保障冲击接地电阻≤10Ω为验收目标。
Grounding resistance target: Per Article 4.2.1, Clause 8 of GB 50057-2010, the impulse grounding resistance of each down conductor of an independent air terminal should not exceed 10Ω. Measured power-frequency resistance shall be converted per Appendix C of GB 50057-2010 before judgment. Jielitong's configuration targets impulse grounding resistance ≤ 10Ω for acceptance.

五、GH-2型产品核心特点

  1. Core Product Features of GH-2

单管锥形结构,外观简洁、占地极小:GH-2为单根锥形钢管,无拉索、无桁架,底盘直径仅362mm,JD-1基础占地不足1平方米。对于楼顶、围墙内、设备旁等空间受限的安装位置,GH-2是GH系列中最“不挑地”的11米级方案之一,与GH-1共享同一套成熟的安装与基础体系。
Single-pipe tapered structure, clean appearance, minimal footprint: GH-2 is a single tapered steel pipe with no guy wires or truss framing. The base plate diameter is only 362mm, and the JD-1 foundation occupies less than 1 square meter. For space-constrained locations such as rooftops, within walls, or beside equipment, GH-2 is one of the most “site-friendly” 11-meter solutions in the GH series, sharing the same mature installation and foundation system as GH-1.

塔体即引下线,省去专用引下线成本与故障点:与桁架塔需要单独敷设扁钢或绞线引下线不同,GH-2的钢管本体直接构成雷电流泄放通路,省去了引下线材料、固定卡扣及长期巡检中“引下线是否松动/锈蚀”的检查环节。只需保证法兰跨接可靠、断接卡测试正常即可。
Tower body as down conductor, eliminating dedicated down-conductor cost and failure points: Unlike truss towers that require separately laid flat steel or stranded wire down conductors, the steel pipe body of GH-2 directly forms the lightning current discharge path, eliminating down-conductor materials, fixing clamps, and the long-term inspection item of “whether the down conductor is loose/corroded.” Only reliable flange bonding and proper disconnect-clamp testing are required.

与GH-1共享基础体系,选型与施工无缝切换:GH-2与GH-1在11米高度、0.4 kN/m²风压、5mm壁厚下参数一致,均采用JD-1基础(650×800mm,埋深2.0m,0.845m³,M24×8)。设计院在出图时无需为GH-2单独调整基础方案,施工单位可直接套用同一套基础图纸,降低了选型与施工的切换成本。
Shares foundation system with GH-1, seamless switching in selection and construction: GH-2 and GH-1 have identical parameters at 11m, 0.4 kN/m², and 5mm wall thickness, both using the JD-1 foundation (650×800mm, 2.0m embedment, 0.845m³, M24×8). Design institutes do not need to adjust foundation drawings separately for GH-2, and construction units can directly use the same foundation drawings, reducing switching costs in selection and construction.

单管塔垂直度按CECS 80专项条款验收,口径明确:GH-2作为单管塔,垂直度验收依据 CECS 80:2006第9.6.2条(≤H/1500) ,而非塔架通用的第9.5.5条。11米高度对应允许偏差 ≤7.3mm。该条款在规范中有单管塔的独立条文支撑,设计院与检测方依据清晰。需注意,部分厂家资料标注的“≤1/1000”为厂家自定值,本文件以CECS 80规范条文为准。
Single-pipe tower verticality accepted per CECS 80 dedicated clause, clear criterion: As a single-pipe tower, GH-2's verticality acceptance is based on Article 9.6.2 of CECS 80:2006 (≤H/1500) , not the general tower-frame Article 9.5.5. For an 11-meter height, the allowable deviation is ≤7.3mm. This criterion is supported by an independent single-pipe tower clause in the code, providing a clear basis for design institutes and testing parties. Note that the “≤1/1000” marked in some manufacturer data is a manufacturer-defined value; this document uses the CECS 80 code provision as the governing criterion.

六、GH-2型适用应用场景

  1. Application Scenarios of GH-2

楼顶与屋顶设备防雷:写字楼、医院、学校等建筑的楼顶空调机组、通信天线、监控设备。GH-2单管结构可在屋面狭小空间内落地或采用法兰基座固定,底盘362mm,对屋面防水层和结构荷载的影响远小于桁架塔。
Rooftop and roof equipment lightning protection: Rooftop air-conditioning units, communication antennas, and monitoring equipment on office buildings, hospitals, and schools. GH-2's single-pipe structure can be floor-mounted or flange-base-fixed in narrow roof spaces, with a 362mm base plate, exerting far less impact on roof waterproofing and structural loads than truss towers.

小型库房与泵房:乡镇物资仓库、农资库、小型水泵房、加油站辅助用房。11米高度足以覆盖单体建筑及周边小范围区域,单管外观简洁,不影响库区整体视觉。
Small warehouses and pump rooms: Township material warehouses, agricultural supply depots, small pump houses, and auxiliary buildings of gas stations. The 11-meter height is sufficient to cover individual buildings and small surrounding areas; the single-pipe appearance is clean and does not affect the overall visual character of the site.

通信基站与野外机房(常规风压区) :内陆微风区的微型基站、中继机房。GH-2占地极小,可直接建在租用的基站院落内或机房侧墙旁,5mm壁厚配置在经济性上具有明显优势。
Communication base stations and field equipment rooms (conventional wind pressure areas): Micro base stations and relay equipment rooms in inland breeze areas. GH-2 has an extremely small footprint and can be built directly within a leased base station courtyard or beside an equipment room wall; the 5mm wall configuration offers clear economic advantages.

场地受限的工业辅助设施:工厂车间旁、围墙边角、管廊附近的局部防雷点位。单管塔无需拉索、无需大根开,在狭窄通道或设备密集区具有桁架塔难以替代的安装便利性。
Space-constrained industrial auxiliary facilities: Localized lightning protection points beside factory workshops, wall corners, or pipe racks. The single-pipe tower requires no guy wires and no large root span, offering installation convenience that truss towers cannot match in narrow passages or equipment-dense areas.

七、验收与运维说明

  1. Acceptance and O&M Instructions

安装验收:核对地勘报告,确认地基承载力特征值满足 ≥100 kN/m²。单管塔整体垂直度偏差 ≤H/1500(≤7.3mm)(CECS 80:2006第9.6.2条)。M24×8地脚螺栓须按力矩要求复紧。法兰连接处须检查跨接可靠性,确保塔体作为引下线的电气连续性。接地系统完工后实测工频电阻并按GB 50057附录C换算,以 冲击接地电阻≤10Ω 为合格判定口径。
Installation acceptance: Check the geotechnical report to confirm foundation bearing capacity ≥100 kN/m². Single-pipe tower verticality deviation ≤H/1500 (≤7.3mm) (CECS 80:2006 Article 9.6.2). M24×8 anchor bolts shall be re-tightened to torque requirements. Flange connections shall be checked for bonding reliability to ensure electrical continuity of the tower body as the down conductor. After grounding system completion, measure power-frequency resistance, convert per Appendix C of GB 50057, and use impulse grounding resistance ≤10Ω as the qualified criterion.

定期巡检:每年雷雨季前检查底盘法兰及中间法兰的螺栓有无松动、锈蚀,跨接导体是否完好。由于无专用引下线,重点检查塔体法兰接续处的电气连通性(可抽测接触电阻)。检查断接卡是否可正常断开。台风或大风过后检查基础周边有无冲刷或积水。
Periodic inspection: Before each thunderstorm season, check base and intermediate flange bolts for loosening and corrosion, and verify bonding conductors are intact. Since there is no dedicated down conductor, focus on the electrical continuity at tower body flange joints (spot-check contact resistance). Check that the disconnect clamp can be properly opened. After typhoons or strong winds, check foundation surroundings for scour or water accumulation.

防腐修补:若镀锌层有磕碰脱落,用 富锌底漆(干膜含锌量≥80%) 补涂两道。锥形钢管底部接近地面区域为腐蚀敏感区,沿海或工业大气项目中建议每5年对该区域进行面漆维护。
Anti-corrosion repair: If the galvanized coating is knocked off, apply two coats of zinc-rich primer (zinc content in dry film ≥80%). The lower portion of the tapered steel pipe near ground level is a corrosion-sensitive zone; for coastal or industrial atmosphere projects, topcoat maintenance of this zone every 5 years is recommended.

智能监测运维:选配的雷电计数器支持长期免维护运行,数据可人工读取或通过物联网模块接入运维平台。
Intelligent monitoring O&M: The optional lightning counter supports long-term maintenance-free operation; data can be read manually or connected to the Jielitong O&M platform via IoT modules.

 

雷百汇实力
20年防雷实力沉淀,打造防雷行业实力企业
20年防雷实力沉淀,打造防雷行业实力企业
雷百汇防雷,专注防雷领域20年,生产防雷设备等相关设备产品,数十种防雷产品系列,拥有多年防雷安装项目经验。
定制防雷解决方案,满足个性化防雷需求
定制防雷解决方案,满足个性化防雷需求
公司凭借强劲的技术实力、优质的防雷技术团队,自成立以来承接各类防雷项目千余项,为您定制专属您的高品质防雷方案。
一站式服务体系,售后无忧
一站式服务体系,售后无忧
雷百汇设有优质服务团队,在售前售中售后等环节竭诚为您服务,全程跟进直至问题解决。一站解决您的需求。
免费定制防雷解决方案

GH-2型11米单管钢管避雷塔技术文档雷百汇防雷向您介绍GH-2型11米单管钢管避雷塔技术文档产品设备价格、设备原理、技术参数、应用领域。同时您还可以查看GH系列环形避雷塔或浏览全部防雷工程案例、新闻资讯,也可以查看相关的服务支持。

最新案例
查看更多案例

地点:

行业:能源煤矿

多系产品,满足定制

多系产品,满足定制

防雷专家,无忧雷电

防雷专家,无忧雷电

动态影像,直观体验

动态影像,直观体验

公司新闻
查看全部
2021.03.15
2021.03.01
© 2012-2017 雷百汇商城   版权所有并保留所有权利 ICP备案证书号:豫ICP备17013924号 技术支持:悉知科技