一、可插拔多极电涌保护器(SPD)产品说明
Pluggable Multi-Pole Surge Protective Device
安装于建筑物总配电柜或雷电流可能进入的电源入口。
Installed in the main distribution boards of buildings or power inlet where lightning current may enter.
主要承受雷电流冲击。
It is mainly used to withstand lightning current surges.
标称为 10/350 μs 波形。
Nominal waveform: 10/350 μs.
适用于有外部防雷系统、存在直接雷电流引入风险的场所。
Suitable for sites with external lightning protection system and risk of direct lightning current intrusion.
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Location of Use |
使用位置 |
Main Distribution Boards 主配电盘 |
|
Network Systems |
适用电网系统 |
TN-S |
|
Mode of Protection |
保护模式 |
L-PE, N-PE |
|
Surge Ratings |
电涌防护等级 |
Iimp = up to 12.5 kA (10/350μs); In = up to 20 kA (8/20μs) |
|
IEC/EN/UL Category |
IEC/EN/UL 分类 |
Class I+II / Type 1+2 / Type 1CA |
|
Protective Elements |
保护元件 |
High Energy MOV 高能压敏电阻 |
|
Housing |
外壳结构 |
Pluggable Design 可插拔式设计 |
|
Compliance |
合规标准 |
IEC 61643-11:2011; EN 61643-11:2012; UL 1449 4th Edition |
二、Technical Data — IEC Electrical | 技术参数 — IEC 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Nominal AC Voltage Uo/Un |
额定交流电压 |
120V / 230V / 277V / 380V / 440V |
|
Max. Continuous Operating Voltage (AC) Uc |
最大持续运行电压(交流) |
150V / 275V / 320V / 385V / 440V |
|
Nominal Discharge Current (8/20 μs) In |
标称放电电流(8/20μs) |
20 kA |
|
Max. Discharge Current (8/20 μs) Imax |
最大放电电流(8/20μs) |
50 kA |
|
Impulse Discharge Current (10/350 μs) Iimp |
冲击放电电流(10/350μs) |
12.5 kA |
|
Specific Energy W/R |
比能量 |
39 kJ/Ω / 25 kJ/Ω |
|
Charge Q |
电荷量 |
6.25 As / 5 As |
|
Voltage Protection Level Up |
电压保护水平 |
1000V / 1500V / 2000V |
|
Response Time tA |
响应时间 |
< 25 ns |
|
Back-Up Fuse (max) |
后备保护熔断器(最大) |
315 A / 250 A gG |
|
Short-Circuit Current Rating IsccR |
短路电流耐受能力 |
25 kA / 50 kA |
|
TOV Withstand 5s UT |
暂时过电压耐受5秒 |
180V / 335V / 580V |
|
TOV 120min Mode |
TOV 120分钟模式 |
Safe Fail 安全失效模式 |
三、Technical Data — UL Electrical | 技术参数 — UL 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Max. Continuous Operating Voltage (AC) MCOV |
最大持续运行电压(MCOV) |
150V / 275V / 320V / 385V / 440V |
|
Voltage Protection Rating VPR |
电压保护额定值(VPR) |
600V / 900V / 1200V / 1350V / 1500V |
|
Nominal Discharge Current (8/20 μs) In |
标称放电电流(8/20μs) |
20 kA |
|
Short-Circuit Current Rating SCCR |
短路电流额定值(SCCR) |
200 kA / 150 kA |
四、内部设置
五、尺寸与包装
六、连接图
七、安装说明 Installation Instruction
安装在室内主配电盘内,采用标准导轨安装,产品为可插拔式设计,便于后期维护更换模块。 Installed in indoor main distribution boards with standard DIN rail mounting. The pluggable design facilitates module replacement and maintenance.
保护模式 L-PE、N-PE,适配 TN-S 电网系统,严格按照相序接线。
Protection modes: L-PE, N-PE, applicable for TN-S power system, wiring shall follow phase sequence strictly.
前端配套后备保护熔断器,最大 315A gG,根据系统短路电流参数选型。
Back-up fuse shall be installed on the upstream, max.315A gG, selected according to system short-circuit current parameters.
PE 保护地线连接至建筑物总等电位端子,接地线短而直,减小引线电感。
PE wire shall connect reliably to the main equipotential terminal of the building. Earthing wire should be short and straight to reduce lead inductance.
安装环境保持干燥通风,远离腐蚀性气体、高温及强振动区域。
Keep installation area dry and ventilated, away from corrosive gas, high temperature and strong vibration.
八、安装场景应用 Application Scenarios
配备外部防雷装置的建筑总电源进线柜,一级电源防雷保护。
Main power incoming cabinet of buildings equipped with external lightning protection system for Class I power lightning protection.
数据中心、通信机房、医院、厂区、大型公共建筑总配电房直击雷防护。
Direct lightning protection for main distribution room of data centers, communication rooms, hospitals, factories and large public buildings.
光伏、风电等新能源项目总配电系统电源入口防雷。
Lightning protection at power inlet of main distribution system for photovoltaic, wind power and other new energy projects.