一、LY1-12.5B/3+NPE 可插拔多极电涌保护器(SPD)产品说明
Pluggable Multi-Pole Surge Protective Device
安装于建筑物总配电柜或雷电流可能进入的电源入口。
Installed in the main distribution boards of buildings or power inlet where lightning current may enter.
主要承受雷电流冲击。
It is mainly used to withstand lightning current surges.
标称为 10/350 μs 波形,冲击放电电流 Iimp=12.5kA。
Nominal waveform: 10/350 μs, Impulse Discharge Current Iimp=12.5kA.
适用于有外部防雷系统、存在直接雷电流引入风险的场所。
Suitable for sites with external lightning protection system and risk of direct lightning current intrusion.
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Location of Use |
使用位置 |
Main Distribution Boards 主配电盘 |
|
Network Systems |
适用电网系统 |
TT, TN-S |
|
Mode of Protection |
保护模式 |
N-PE, L-N |
|
Surge Ratings |
电涌防护等级 |
Iimp = 12.5 kA (10/350μs); In = 20 kA (8/20μs) |
|
IEC/EN/UL Category |
IEC/EN/UL 分类 |
Class I+II / Type 1+2 / Type 1CA |
|
Protective Elements |
保护元件 |
High Energy MOV and GDT 高能压敏电阻+气体放电管 |
|
Housing |
外壳结构 |
Pluggable Design 可插拔式设计 |
|
Compliance |
合规标准 |
IEC 61643-11:2025; EN 61643-11:2025; UL 1449 4th Edition |
二、Technical Data — IEC Electrical | 技术参数 — IEC 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Nominal AC Voltage (L-N) Uc |
额定交流电压(L-N) |
120V / 230V / 380V |
|
Max. Continuous Operating Voltage (L-N) Uc |
最大持续运行电压(L-N) |
150V / 275V / 385V |
|
Max. Continuous Operating Voltage (N-PE) Uc |
最大持续运行电压(N-PE) |
255V |
|
Nominal Discharge Current (L-N)/(N-PE) In |
标称放电电流 |
20 kA / 50 kA |
|
Max. Discharge Current (L-N)/(N-PE) Imax |
最大放电电流 |
50 kA / 100 kA |
|
Impulse Discharge Current (L-N)/(N-PE) Iimp |
冲击放电电流 |
12.5 kA / 50 kA |
|
Specific Energy W/R |
比能量 |
39 kJΩ / 625 kJΩ |
|
Charge Q |
电荷量 |
6.25 As / 25 As |
|
Voltage Protection Level (L-N)/(N-PE) Up |
电压保护水平 |
1500V |
|
Follow Current Interrupting Rating (N-PE) Ifi |
后续电流开断能力(N-PE) |
100 Arms |
|
Response Time (L-N)/(N-PE) tA |
响应时间 |
< 25 ns / < 100 ns |
|
Back-Up Fuse (max) |
后备保护熔断器(最大) |
315 A gL/gG |
|
Short-Circuit Current Rating (L-N) IsccR |
短路电流耐受能力(L-N) |
25 kA / 50 kA |
|
TOV Withstand 5s (L-N) UT |
暂时过电压耐受5秒(L-N) |
180V / 335V / 335V |
|
TOV 120min Mode (L-N) |
TOV 120分钟模式 |
Safe Fail 安全失效 |
|
TOV Withstand 200ms (N-PE) UT |
暂时过电压耐受200ms(N-PE) |
1200V |
三、内部设置
四、尺寸与包装
五、连接图
六、安装说明 Installation Instruction
产品为可插拔式结构,采用标准 DIN 导轨安装于室内主配电盘,模块可单独插拔,检修更换便捷。
The product adopts pluggable structure, mounted on standard DIN rail inside indoor main distribution board. Modules can be plugged and pulled separately for convenient maintenance and replacement.
保护模式:N-PE、L-N,适配 TT、TN-S 电网系统,严格按照相序规范接线。
Protection modes: N-PE, L-N, applicable for TT and TN-S power systems. Wiring shall follow phase sequence specifications strictly.
前端需配置后备保护熔断器,最大 315A gL/gG,熔断器选型应匹配配电系统短路参数。
Back-up fuse shall be equipped on the upstream, max.315A gL/gG. Fuse selection shall match short-circuit parameters of the distribution system.
PE 保护地线可靠连接至建筑物总等电位接地端子,接地线尽量短直,降低引线电感。
PE protective earth wire shall be reliably connected to the main equipotential terminal of the building. Earthing conductor shall be as short and straight as possible to reduce lead inductance.
安装环境要求干燥通风,避开潮湿、腐蚀、高温及强振动区域。
The installation environment shall be dry and ventilated, away from humid, corrosive, high-temperature and strong vibration areas.
七、安装场景应用 Application Scenarios
设有外部防雷装置建筑的总电源进线柜,用于一级电源直击雷防护。
Main power incoming cabinet of buildings equipped with external lightning protection system, for Class I direct lightning protection of power supply.
数据中心、通信机房、医院、工厂、大型公共建筑总配电房电源入口防雷保护。
Lightning protection for power inlet in main distribution rooms of data centers, communication rooms, hospitals, factories and large public buildings.
光伏、风电等新能源项目主配电系统进线端直击雷防护。
Direct lightning protection for incoming line of main distribution system in photovoltaic, wind power and other new energy projects.