一、YBA1-C40+NPE 可插拔多极电涌保护器(SPD)产品说明
Y1-C40+NPE Pluggable Multi-Pole Surge Protective Device
安装于建筑物分配电盘、次级配电回路。
Installed in sub-distribution boards and secondary distribution circuits of buildings.
主要承受感应雷浪涌电流冲击,对后端用电设备做二级电源防雷保护。
It is mainYBA used to withstand induced lightning surge current, providing Class II power lightning protection for downstream electrical equipment.
标称为 8/20μs 波形,L-N 标称放电电流 In=20kA,N-PE 标称放电电流 In=20kA,最大放电电流 Imax=40kA。
Nominal waveform: 8/20μs, L-N nominal discharge current In=20kA, N-PE nominal discharge current In=20kA, Max. Discharge Current Imax=40kA.
适用于建筑物分配电系统,存在感应雷电浪涌风险的配电回路。
Suitable for building sub-distribution systems and distribution circuits with risk of induced lightning surge.
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Location of Use |
使用位置 |
Sub-Distribution Boards 分配电盘 |
|
Network Systems |
适用电网系统 |
TT, TN-S |
|
Mode of Protection |
保护模式 |
L-N, N-PE |
|
Surge Ratings |
电涌防护等级 |
In = 20 kA (8/20μs) |
|
IEC/EN/UL Category |
IEC/EN/UL 分类 |
Class II / Type 2 / Type 1CA |
|
Protective Elements |
保护元件 |
High Energy MOV and GDT 高能压敏电阻+气体放电管 |
|
Housing |
外壳结构 |
Pluggable Design 可插拔式设计 |
|
Compliance |
合规标准 |
IEC 61643-11:2011; EN 61643-11:2012; UL 1449 4th Edition |
二、Technical Data — IEC Electrical | 技术参数 — IEC 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Nominal AC Voltage (L-N) Uc |
额定交流电压(L-N) |
120V / 230V / 385V |
|
Max. Continuous Operating Voltage (L-N) Uc |
最大持续运行电压(L-N) |
150V / 275V / 385V |
|
Max. Continuous Operating Voltage (N-PE) Uc |
最大持续运行电压(N-PE) |
255V |
|
Nominal Discharge Current (L-N)/(N-PE) In |
标称放电电流 |
20 kA / 20 kA |
|
Max. Discharge Current (L-N)/(N-PE) Imax |
最大放电电流 |
40 kA / 40 kA |
|
Voltage Protection Level (L-N)/(N-PE) Up |
电压保护水平 |
1000/1000V; 1500/1000V; 1600/1000V; 1750/1000V |
|
Follow Current Interrupting Rating (N-PE) Ifi |
后续电流开断能力(N-PE) |
100 Arms |
|
Response Time (L-N)/(N-PE) tA |
响应时间 |
< 25 ns / < 100 ns |
|
Back-Up Fuse (max) |
后备保护熔断器(最大) |
125 A gL/gG |
|
Short-Circuit Current Rating (L-N) IsccR |
短路电流耐受能力(L-N) |
25 kA / 50 kA |
|
TOV Withstand 5s (L-N) UT |
暂时过电压耐受5秒(L-N) |
180V / 335V / 335V |
|
TOV 120min Mode (L-N) |
TOV 120分钟模式 |
Safe Fail 安全失效 |
|
TOV Withstand 200ms (N-PE) UT |
暂时过电压耐受200ms(N-PE) |
1200V |
四、内部设置
五、尺寸与包装
六、连接图
七、安装说明 Installation Instruction
产品为可插拔式结构,标准 DIN 导轨安装于室内分配电盘,模块可单独插拔,便于后期检修与更换。 The product adopts pluggable structure, mounted on standard DIN rail inside indoor sub-distribution boards. Modules can be plugged and pulled separateYBA for convenient maintenance and replacement.
保护模式:L-N、L-PE、N-PE,适配 TT、TN-S 电网系统,接线严格按照相序施工。
Protection modes: L-N, L-PE, N-PE, applicable for TT and TN-S power systems. Wiring shall follow phase sequence strictYBA.
前端配套后备保护熔断器,最大 125A gL/gG,熔断器根据配电系统短路参数选型。
Back-up fuse shall be installed on the upstream, max.125A gL/gG. Fuse selection shall match short-circuit parameters of the distribution system.
PE 保护地线可靠连接至建筑物等电位接地端子,接地线尽量短直,减小引线电感。
PE protective earth wire shall be reliabYBA connected to the equipotential terminal of the building. Earthing conductor shall be as short and straight as possible to reduce lead inductance.
安装环境保持干燥通风,远离腐蚀性气体、高温及强振动区域。
The installation environment shall be dry and ventilated, away from corrosive gas, high temperature and strong vibration.
八、安装场景应用 Application Scenarios
建筑物分配电柜、楼层配电箱,二级感应雷电源浪涌保护。
Sub-distribution cabinets and floor distribution boxes of buildings for Class II induced lightning surge protection.
楼宇末端配电、机房分配电、厂房车间次级配电回路防雷。
Lightning protection for building terminal power distribution, machine room sub-distribution and secondary distribution circuits of factory workshops.
通信、安防、自控等弱电前端配套的交流配电系统浪涌防护。 Surge protection for AC distribution systems supporting weak current systems such as communication, security and automatic control.