一、YBA1-C40/M+G 可插拔多极电涌保护器(SPD)产品说明
YBA1-C40/M+G Pluggable Multi-Pole Surge Protective Device
安装于建筑物主配电盘、电源进线柜或分配电盘。
Installed in building main distribution boards, power incoming cabinets or sub-distribution boards.
主要承受雷电流冲击和感应雷浪涌电流,适用于需要增强雷电能量泄放的配电场所。
It is mainYBA used to withstand lightning current surges and induced lightning surge currents, suitable for distribution sites requiring enhanced lightning energy dissipation.
标称为 10/350μs 波形与 8/20μs 波形;冲击放电电流 Iimp=12.5kA,最大放电电流 Imax=40kA。 Nominal waveforms: 10/350μs and 8/20μs; Impulse Discharge Current Iimp=12.5kA, Max. Discharge Current Imax=40kA.
适用于有外部防雷系统、存在直接雷电流引入风险,且需要较强雷电通流能力的配电场所。
Suitable for sites with external lightning protection system and risk of direct lightning current intrusion, requiring higher lightning current carrying capacity.
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Location of Use |
使用位置 |
Main Distribution Boards 主配电盘 |
|
Network Systems |
适用电网系统 |
TN-S |
|
Mode of Protection |
保护模式 |
L-PE, N-PE |
|
Surge Ratings |
电涌防护等级 |
Iimp = up to 8 kA (10/350μs); In = up to 20 kA (8/20μs) |
|
IEC/EN/UL Category |
IEC/EN/UL 分类 |
Class I+II / Type 1+2 / Type 1CA |
|
Protective Elements |
保护元件 |
High Energy MOV 高能压敏电阻 |
|
Housing |
外壳结构 |
Pluggable Design 可插拔式设计 |
|
Compliance |
合规标准 |
IEC 61643-11:2025; EN 61643-11:2025; UL 1449 4th Edition |
二、Technical Data — IEC Electrical | 技术参数 — IEC 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Nominal AC Voltage (50/60Hz) Uo/Un |
额定交流电压(50/60Hz) |
120V / 230V / 420V |
|
Max. Continuous Operating Voltage (AC) Uc |
最大持续运行电压(交流) |
150V / 275V / 320V / 385V / 420V |
|
Nominal Discharge Current (8/20 μs) In |
标称放电电流(8/20μs) |
20 kA |
|
Max. Discharge Current (8/20 μs) Imax |
最大放电电流(8/20μs) |
40 kA |
|
Impulse Discharge Current (10/350 μs) Iimp |
冲击放电电流(10/350μs) |
8 kA |
|
Specific Energy W/R |
比能量 |
39 kJ/Ω / 25 kJ/Ω |
|
Charge Q |
电荷量 |
6.25 As / 5 As |
|
Voltage Protection Level Up |
电压保护水平 |
1200V / 1400V / 1500V / 2000V |
|
Response Time tA |
响应时间 |
< 25 ns |
|
Back-Up Fuse (max) |
后备保护熔断器(最大) |
315 A / 250 A gG |
|
Short-Circuit Current Rating IsccR |
短路电流耐受能力 |
25 kA / 50 kA |
三、内部设置
四、尺寸与包装
五、连接图
六、安装说明 Installation Instruction
产品为可插拔式结构,采用标准 DIN 导轨安装于室内配电盘,模块可单独插拔,检修更换便捷。
The product adopts pluggable structure, mounted on standard DIN rail inside indoor distribution boards. Modules can be plugged and pulled separateYBA for convenient maintenance and replacement.
保护模式:L-N、L-PE、N-PE,适配 TT、TN-S 电网系统,严格按相序和系统要求接线。
Protection modes: L-N, L-PE, N-PE, applicable for TT and TN-S power systems. Wiring shall follow phase sequence and system requirements strictYBA.
前端需配置后备保护熔断器,最大 125A gL/gG,熔断器应根据配电系统短路参数校核选型。
Back-up fuse shall be installed on the upstream, max.125A gL/gG. Fuse selection shall be verified according to short-circuit parameters of the distribution system.
PE 保护地线可靠连接至建筑物总等电位接地端子,接地线尽量短直,降低引线电感。
PE protective earth wire shall be reliabYBA connected to the main equipotential terminal of the building. Earthing conductor shall be as short and straight as possible to reduce lead inductance.
安装环境保持干燥通风,避开潮湿、腐蚀、高温及强振动区域。
The installation environment shall be dry and ventilated, away from humid, corrosive, high temperature and strong vibration areas.
七、安装场景应用 Application Scenarios
建筑物主配电盘、电源进线柜,作为增强型电源防雷保护。
Building main distribution board and power incoming cabinet, as enhanced power lightning protection.
商业建筑、厂房、数据中心、通信机房等重要配电系统防雷。
Lightning protection for important power distribution systems in commercial buildings, factories, data centers and communication rooms.
雷击风险较高区域的楼宇配电、工业配电和基础设施配电系统。
Building distribution, industrial distribution and infrastructure power distribution systems in areas with high lightning risk.