一、YBA-C40/3+NPE 可插拔多极电涌保护器(SPD)产品说明
YBA-C40/3+NPE Pluggable Multi-Pole Surge Protective Device
安装于建筑物分配电盘、次级配电回路或三相四线制配电系统。 Installed in building sub-distribution boards, secondary distribution circuits or three-phase four-wire power distribution systems.
主要承受感应雷浪涌电流冲击,对后端三相四线制配电设备提供二级电源防雷保护。 It is mainly used to withstand induced lightning surge currents and provide Class II power lightning protection for downstream three-phase four-wire distribution equipment.
标称为 8/20μs 波形,最大放电电流 Imax=40kA。 Nominal waveform: 8/20μs, Max. Discharge Current Imax=40kA.
适用于 TT、TN-S 系统三相四线制配电场所,存在感应雷电浪涌风险的建筑物配电回路。 Suitable for three-phase four-wire distribution sites with TT and TN-S systems, and building distribution circuits where induced lightning surge risk exists.
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Location of Use |
使用位置 |
Sub-Distribution Boards 分配电盘 |
|
Network Systems |
适用电网系统 |
TT, TN-S |
|
Mode of Protection |
保护模式 |
L-N, N-PE |
|
Surge Ratings |
电涌防护等级 |
In = 20 kA (8/20μs) |
|
IEC/EN/UL Category |
IEC/EN/UL 分类 |
Class II / Type 2 / Type 1CA |
|
Protective Elements |
保护元件 |
High Energy MOV and GDT 高能压敏电阻+气体放电管 |
|
Housing |
外壳结构 |
Pluggable Design 可插拔式设计 |
|
Compliance |
合规标准 |
IEC 61643-11:2025; EN 61643-11:2025; UL 1449 4th Edition |
二、Technical Data — IEC Electrical | 技术参数 — IEC 电气参数
|
Parameter (EN) |
参数名称 (中文) |
Spec / 规格 |
|
Nominal AC Voltage (L-N) Uc |
额定交流电压(L-N) |
120V / 230V / 385V |
|
Max. Continuous Operating Voltage (L-N) Uc |
最大持续运行电压(L-N) |
150V / 275V / 385V |
|
Max. Continuous Operating Voltage (N-PE) Uc |
最大持续运行电压(N-PE) |
255V |
|
Nominal Discharge Current (L-N)/(N-PE) In |
标称放电电流 |
20 kA / 20 kA |
|
Max. Discharge Current (L-N)/(N-PE) Imax |
最大放电电流 |
40 kA / 40 kA |
|
Voltage Protection Level (L-N)/(N-PE) Up |
电压保护水平 |
1000/1000V; 1500/1000V; 1600/1000V; 1750/1000V |
|
Follow Current Interrupting Rating (N-PE) Ifi |
后续电流开断能力(N-PE) |
100 Arms |
|
Response Time (L-N)/(N-PE) tA |
响应时间 |
< 25 ns / < 100 ns |
|
Back-Up Fuse (max) |
后备保护熔断器(最大) |
125 A gL/gG |
|
Short-Circuit Current Rating (L-N) IsccR |
短路电流耐受能力(L-N) |
25 kA / 50 kA |
|
TOV Withstand 5s (L-N) UT |
暂时过电压耐受5秒(L-N) |
180V / 335V / 335V |
|
TOV 120min Mode (L-N) |
TOV 120分钟模式 |
Safe Fail 安全失效 |
|
TOV Withstand 200ms (N-PE) UT |
暂时过电压耐受200ms(N-PE) |
1200V |
三、内部配置
四、尺寸与包装
五、连接图
六、安装说明 Installation Instruction
七、安装场景应用 Application Scenarios
楼宇配电、工业配电和基础设施配电回路的感应雷浪涌保护。 Induced lightning surge protection for building distribution, industrial distribution and infrastructure power distribution circuits.